Condition Monitoring System - CMS
 

The CMS is the most efficient devices in its class. Small and large applications can be realized by interconnecting Master and Slave units each equipped with one or two I/O modules which can be freely combined. Up to 48 slaves with similar housing design can be connected to a Master device via CAN-bus. The system offers a unique linking between analog and digital world. The device do not require much space and easy to mount on DIN rail for integration into an existing enclosure. 

Each device works independently and are therefore not dependent upon network or PC. Data and settings are kept in the local memory of the Master unit. With the compact and modular sub-system, it is now possible to monitor machinery vibrations, air gap, cavitation and process statistics, such as temperature and pressure, at the same time, within one system. The powerful Ethernet connection (TCP / IP), RS232 / 485 link and software drivers make it easy to build factory condition monitoring system with almost all kinds of existing systems.

 

 

 

 

Applications

- On-line vibration monitoring at machines,   aggregates and plants of all types.

- Vibration measurements at turbo and hydrogenerator sets and electrical motors.

- Relative vibration measurements at turbo and hydrogenerator sets and electrical motors acc. to ISO 7919/1-5 and VDI 2059.

- Absolute vibration measurements at turbo and hydrogenerator sets and electrical motors inc. endwindings vibration acc. to ISO 10816/1/1-5.

- Air Gap protection and monitoring .

- Cavitation monitoring.

- Operating parameter monitoring.  

 

Features

- Modular and expandable with up to 48 slave units.

- DIN rail mount, small size.

- CAN-bus data transmission between units.

- Ethernet/TCP-IP for local area network.

- RS-232/RS-485 communication link.

- Full programming by means of pushbuttons or PC link Ethernet / RS.

- Two slots for dedicated in/out modules.

- + 24 VDC Power Supply.

- OPC driver and Labview driver for data exchange with OPC client.

Technical Data for one Basic Module

DSP

Digital Signal Processor (DSP), with local signal memory. 

Input

8 synchronous/parallel sampled analog inputs (14 Bit, +/-10V), can be freely expanded.  

Sample Rate

Sampling frequency max. 25/50 kHz, useful signal bandwidth DC-10 kHz. 

Trigger

Triggered recording with max. 8192 points (per channel). 

Digital Filter

1Digital filters (low pass/band pass/high pass) up to 10th order. 

Spectrum

FFT analysis (in device) with 100/400/1600 lines. 

Fluid pressure

Vibration characteristics, broad and narrow band. 

Analog Output

2 analog outputs +/-10V, can be freely expanded. 

Status Input

4 status inputs, can be freely expanded.  

Switching Output

4 switching outputs, can be freely expanded

Physical Dimensions

Face: 200 mm x 75 mm, Depth: 125 mm.